Violation Detail
Standard Cited: 19100303 B02 General.
Inspection Nr: 1332598.015
Citation: 01006A
Citation Type: Serious
Abatement Date: 01/08/2019 2
Initial Penalty: $5,174.00
Current Penalty: $3,500.00
Issuance Date: 11/19/2018
Nr Instances: 1
Nr Exposed: 3
Related Event Code (REC): C
Gravity: 5
Report ID: 0112000
Contest Date:
Final Order: 12/06/2018
Emphasis:
Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
---|---|---|---|---|---|---|
Penalty | I: Informal Settlement | 12/06/2018 | $3,500.00 | 01/08/2019 | Serious | |
Penalty | Z: Issued | 11/19/2018 | $5,174.00 | 01/08/2019 | Serious |
Text For Citation: 01 Item/Group: 006A Hazard:
29 CFR 1910.303(b)(2): Listed or labeled electrical equipment was not used or installed in accordance with instructions included in the listing or labeling: WELDING AREA On, or about, July 24, 2018, a relocatable power tap was used in series with a green extension cord to energize a Chicago Electric Welding, 90 amp flux welder and several lamps along the work station. The relocatable power tap was rated for 15 amps and the welder alone was rated for 20 amps.