Violation Detail
Standard Cited: 19100304 G05 Wiring design and protection.
Inspection Nr: 1326689.015
Citation: 01005C
Citation Type: Serious
Abatement Date: 11/28/2018 2
Initial Penalty: $0.00
Current Penalty: $0.00
Issuance Date: 10/10/2018
Nr Instances: 3
Nr Exposed: 10
Related Event Code (REC):
Gravity: 1
Report ID: 0112000
Contest Date:
Final Order: 10/30/2018
Emphasis:
Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
---|---|---|---|---|---|---|
Penalty | I: Informal Settlement | 10/30/2018 | $0.00 | 11/28/2018 | Serious | |
Penalty | Z: Issued | 10/10/2018 | $0.00 | 11/28/2018 | Serious |
Text For Citation: 01 Item/Group: 005C Hazard:
29 CFR 1910.304(g)(5): The path to ground from circuits, equipment, and enclosures was not permanent, continuous, and effective: A. On or about July 20, 2018: In the following locations, electrical equipment was not properly grounded, exposing employees to electric shock hazards: 1. At the door to the Bedding Warehouse, a 31-inch diameter Maxx Aire High Velocity metal-encased orange floor fan did not have a grounding pin. Voltage was detected in the metal enclosure of the fan. 2. In the Office Kitchen Area, voltage was detected in the metal parts of the large white refrigerator, Number 1012419. 3. In the Office Kitchen Area, a 46-inch diameter Autumaire metal-encased black floor fan did not have a grounding pin. Voltage was detected in the metal enclosure of the fan.