Violation Detail
Standard Cited: 19100303 B07 I General.
Inspection Nr: 1305012.015
Citation: 02001
Citation Type: Other
Abatement Date: 10/29/2018 2
Initial Penalty: $0.00
Current Penalty: $0.00
Issuance Date: 09/20/2018
Nr Instances: 1
Nr Exposed: 5
Related Event Code (REC):
Gravity:
Report ID: 0521400
Contest Date:
Final Order: 10/09/2018
Emphasis:
Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
---|---|---|---|---|---|---|
Penalty | I: Informal Settlement | 10/09/2018 | $0.00 | 10/29/2018 | Other | |
Penalty | Z: Issued | 09/20/2018 | $0.00 | 10/29/2018 | Other |
Text For Citation: 02 Item/Group: 001 Hazard:
29 CFR 1910.303(b)(7)(i): Unused openings in boxes, raceways, auxiliary gutters, cabinets, equipment cases, or housings shall be effectively closed to afford protection substantially equivalent to the wall of the equipment: Plant no. 9 (Streator, Illinois), selecting area, by H2 FP3 inspection line's infeed conveyor: on or about March 27, 2018, process checkers/inspectors were exposed to contact with live parts likely to result in serious injury when walking-by and performing general housekeeping tasks around the electrical cutout box no. 3 that had two openings at the top from missing knockouts. Abatement documentation is required for this item in accordance with the requirements of 29 CFR 1903.19(d).