Violation Detail
Standard Cited: 19100147 D03 The control of hazardous energy (lockout/tagout).
Inspection Nr: 1296897.015
Citation: 01001B
Citation Type: Serious
Abatement Date: 3
Initial Penalty: $0.00
Current Penalty: $0.00
Issuance Date: 04/30/2018
Nr Instances: 1
Nr Exposed: 1
Related Event Code (REC): A
Gravity: 10
Report ID: 0522300
Contest Date:
Final Order: 05/23/2018
Emphasis:
Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
---|---|---|---|---|---|---|
Penalty | I: Informal Settlement | 05/23/2018 | $0.00 | Serious | ||
Penalty | Z: Issued | 04/30/2018 | $0.00 | Serious |
Text For Citation: 01 Item/Group: 001B Hazard:
29 CFR 1910.147(d)(3): All energy isolating devices that were needed to control the energy to the machine or equipment were not physically located and operated in such a manner as to isolate the machine or equipment from the energy source(s): On or about February 12, 2018 the employer failed to ensure that the energy isolating devices of the office air handling unit were located and operated to isolate the energy sources. An employee was tasked with servicing the unit without controlling the hazardous energies prior to performing the work. The employee only utilized the on/off switch located at the control panel. Hazardous energy sources include steam, kinetic and electrical.