Violation Detail
Standard Cited: 19100107 C06 Spray finishing using flammable and combustible materials.
Inspection Nr: 1219419.015
Citation: 01002E
Citation Type: Other
Abatement Date: 03/19/2018 2
Initial Penalty: $0.00
Current Penalty: $0.00
Issuance Date: 07/28/2017
Nr Instances: 1
Nr Exposed: 10
Related Event Code (REC):
Gravity:
Report ID: 0523400
Contest Date: 08/22/2017
Final Order: 01/19/2018
Emphasis:
Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
---|---|---|---|---|---|---|
Penalty | F: Formal Settlement | 01/19/2018 | $0.00 | 03/19/2018 | Other | |
Penalty | C: Contested | 08/30/2017 | $0.00 | 08/09/2017 | Serious | |
Penalty | Z: Issued | 07/28/2017 | $0.00 | 08/09/2017 | Serious |
Text For Citation: 01 Item/Group: 002E Hazard:
29 CFR 1910.107(c)(6): Electrical wiring, motors, and other equipment outside of but within twenty (20) feet of any spray area, and not separated therefrom by partitions, produced sparks under normal operating conditions and did not otherwise conform to the provisions of subpart S of this part for Class I, Division 2 Hazardous Locations: (a) The switch mounted on the left side of the paint booth that turns on the paint booth fan and the paint sprayer pump was not approved for that class 1 division 2 hazardous location.