Violation Detail
Standard Cited: 19100107 C06 Spray finishing using flammable and combustible materials.
Inspection Nr: 1174651.015
Citation: 01002B
Citation Type: Serious
Abatement Date: 03/31/2017 2
Initial Penalty: $11,224.00
Current Penalty: $0.00
Issuance Date: 01/12/2017
Nr Instances: 2
Nr Exposed: 3
Related Event Code (REC): C
Gravity: 10
Report ID: 0524530
Contest Date:
Final Order: 02/03/2017
Emphasis:
Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
---|---|---|---|---|---|---|
Penalty | I: Informal Settlement | 02/03/2017 | $0.00 | 03/31/2017 | Serious | |
Penalty | Z: Issued | 01/12/2017 | $11,224.00 | 02/08/2017 | Serious |
Text For Citation: 01 Item/Group: 002B Hazard:
29 CFR 1910.107(c)(6): Electrical wiring and equipment not subject to deposits of combustible residues but located in a spraying area as herein defined were not explosion-proof type approved for Class I, group D locations and did not otherwise conform to the provisions of subpart S of this part, for Class I, Division 1, Hazardous Locations: In spray booths #1 and #3, electrical wiring and equipment such as but not limited to overhead lighting not subject to deposits of combustible residues but located in a spraying area were not explosion-proof type approved for Class I, group D locations and did not otherwise conform to the provisions of subpart S of this part, for Class I, Division 1, Hazardous Locations.