Violation Detail
Standard Cited: 19100303 F02 General.
Inspection Nr: 1148175.015
Citation: 02003
Citation Type: Other
Abatement Date: 3
Initial Penalty: $0.00
Current Penalty: $0.00
Issuance Date: 07/27/2016
Nr Instances: 1
Nr Exposed: 4
Related Event Code (REC):
Gravity:
Report ID: 0112000
Contest Date:
Final Order: 08/16/2016
Emphasis:
Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
---|---|---|---|---|---|---|
Penalty | I: Informal Settlement | 08/16/2016 | $0.00 | Other | ||
Penalty | Z: Issued | 07/27/2016 | $0.00 | Other |
Text For Citation: 02 Item/Group: 003 Hazard:
29 CFR 1910.303(f)(2): Each service, feeder, and branch circuit, at its disconnecting means or overcurrent device, was not legibly marked to indicate its purpose, nor located and arranged so the purpose was evident: Mold Room: On, or about, May 25, 2016, branch circuits provided on the Sylvania panelboard were not labeled to indicate their purpose.