Violation Detail
Standard Cited: 19100305 B01 I Wiring methods, components, and equipment for general use.
Inspection Nr: 1135451.015
Citation: 01003A
Citation Type: Serious
Abatement Date: 09/08/2016 2
Initial Penalty: $4,498.00
Current Penalty: $3,000.00
Issuance Date: 08/26/2016
Nr Instances: 2
Nr Exposed: 4
Related Event Code (REC):
Gravity: 1
Report ID: 0418100
Contest Date: 09/22/2016
Final Order: 07/20/2017
Emphasis:
Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
---|---|---|---|---|---|---|
Penalty | J: ALJ Decision | 07/20/2017 | $3,000.00 | 09/08/2016 | Serious | |
Penalty | C: Contested | 09/23/2016 | $4,498.00 | 09/08/2016 | Serious | |
Penalty | Z: Issued | 08/26/2016 | $4,498.00 | 09/08/2016 | Serious |
Text For Citation: 01 Item/Group: 003A Hazard:
29 CFR 1910.305(b)(1)(i): Conductors entering cutout boxes, cabinets, or fittings were not protected from abrasion, and openings through which conductors enter were not effectively closed. a. On or about March 28, 2016 employees operating the "Powermatic" table saw in the Trim Room were exposed to electrical hazards where electrical conductors entering the bottom of a "Furnas" electrical box attached to the table saw were not protected from abrasion. b. On or about March 28, 2016 employees operating the "Powermatic" table saw in the Trim Room were exposed to electrical hazards where an opening through which conductors entered on the side of the "Furnas" box attached to the table saw was not effectively closed and the conductors entering were not protected from abrasion.