Violation Detail
Standard Cited: 19100107 C06 Spray finishing using flammable and combustible materials.
Inspection Nr: 1118458.015
Citation: 01005
Citation Type: Serious
Abatement Date: 08/29/2016 2
Initial Penalty: $6,300.00
Current Penalty: $4,380.00
Issuance Date: 06/01/2016
Nr Instances: 2
Nr Exposed: 8
Related Event Code (REC):
Gravity: 10
Report ID: 0419400
Contest Date:
Final Order: 06/23/2016
Emphasis:
Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
---|---|---|---|---|---|---|
Penalty | I: Informal Settlement | 06/23/2016 | $4,380.00 | 08/29/2016 | Serious | |
Penalty | Z: Issued | 06/01/2016 | $6,300.00 | 06/16/2016 | Serious |
Text For Citation: 01 Item/Group: 005 Hazard:
29 CFR 1910.107(c)(6): Electrical wiring and equipment not subject to deposits of combustible residues but located in a spraying area as herein defined were not explosion-proof type approved for Class I, group D locations and did not otherwise conform to the provisions of subpart S of this part, for Class I, Division 1, Hazardous Locations: (a) Facility - On or about January 27, 2016 the lighting, electrical panels, receptacles and equipment in the following locations were not rated for Class 1, Division 1 areas. (i) R & D Spray Area - On or about January 27, 2016 electrical receptacles, electrical panels on the outside of the paint booth, bench grinder and battery chargers on work table within 20 feet of the spray area were not explosion proof. (ii) Lamination Small Parts - On or about January 27, 2016 electrical panels, electrical disconnects and exhaust fan on the wall between the ventilation systems were within 20 feet of the spray area and were not explosion proof. (ii) Lamination Molding Paint Booths - On or about January 27, 2016 fluorescent light fixtures and wiring were not explosion proof. Gel coat residue was on the light fixtures and on the wall at or above the light fixtures. (iv) Mixing Room - On or about January 27, 2016 fluorescent light fixture, orange extension cord and radio was not explosion proof.