Violation Detail
Standard Cited: 19100303 G01 I General.
Inspection Nr: 1118005.015
Citation: 02002A
Citation Type: Repeat
Abatement Date: 06/30/2016 4
Initial Penalty: $15,400.00
Current Penalty: $15,400.00
Issuance Date: 06/06/2016
Nr Instances: 4
Nr Exposed: 4
Related Event Code (REC): C
Gravity: 10
Report ID: 0112000
Contest Date:
Final Order: 06/30/2016
Emphasis:
Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
---|---|---|---|---|---|---|
Penalty | Z: Issued | 06/06/2016 | $15,400.00 | 06/30/2016 | Repeat |
Text For Citation: 02 Item/Group: 002A Hazard:
29 CFR 1910.303(g)(1)(i): The employer does not maintain work space that is 30 inches wide in front of electric equipment operating at 600 volts, nominal, or less: This violation was observed on or about January 14, 2016 in the Fabrication and Main Shop Areas where the work space in front of a 120/208 volt electrical panel is reduced to 24 inches by the placement of the Hypertherm Max 200 Plasma Machine. The Press Brake and Shear machines were located in front of and near electrical panels which reduced access to less than 30 inches wide in the machine areas. To abate this violation, the employer must relocate the equipment blocking access to the electrical panels. The Jarosz Welding Co. Inc. was previously cited for a violation of this occupational safety and health standard or its equivalent standard 29 CFR 1910.303(g)(1)(i), which was contained in OSHA inspection number 910472, citation number 1, item number 1a and was affirmed as a final order on March 6, 2014, with respect to a workplace located at 544 Ledyard Street, Hartford, CT. 06114.