Violation Detail
Standard Cited: 19100106 D04 III Flammable liquids.
Inspection Nr: 1117550.015
Citation: 01002
Citation Type: Other
Abatement Date: 04/11/2016 2
Initial Penalty: $6,300.00
Current Penalty: $4,725.00
Issuance Date: 03/09/2016
Nr Instances: 1
Nr Exposed: 3
Related Event Code (REC):
Gravity:
Report ID: 0418200
Contest Date:
Final Order: 03/30/2016
Emphasis:
Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
---|---|---|---|---|---|---|
Penalty | I: Informal Settlement | 03/30/2016 | $4,725.00 | 04/11/2016 | Other | |
Penalty | Z: Issued | 03/09/2016 | $6,300.00 | 04/11/2016 | Serious |
Text For Citation: 01 Item/Group: 002 Hazard:
29 CFR 1910.106(d)(4)(iii): Electrical wiring and equipment located in inside storage rooms used for Category 1 or 2 flammable liquids, or Category 3 flammable liquids with a flashpoint below 100 °F (37.8 °C), was not approved under subpart S of this part for Class I, Division 2 Hazardous Locations; for Category 3 flammable liquids with a flashpoint at or above 100 °F (37.8 °C) and Category 4 flammable liquids, was not approved for general use. a) The production area - The employer stores a partial barrel of MEK and isopropyl alcohol as well as a full barrel of isopropyl alcohol and a barrel containing used MEK in an open area of the production area near the break area with general electrical wiring and appliances, such as but not limited to, a microwave and a Coke Machine nearby.