Violation Detail
Standard Cited: 19100110 H06 I A Storage and handling of liquefied petroleum gases.
Inspection Nr: 1090999.015
Citation: 01004A
Citation Type: Serious
Abatement Date: 01/01/2018 2
Initial Penalty: $1,600.00
Current Penalty: $400.00
Issuance Date: 03/08/2016
Nr Instances: 1
Nr Exposed: 1
Related Event Code (REC):
Gravity: 5
Report ID: 0418400
Contest Date: 03/28/2016
Final Order: 09/12/2016
Emphasis:
Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
---|---|---|---|---|---|---|
Penalty | P: Petition to Mod Abatement | $400.00 | 01/01/2018 | Serious | ||
Penalty | F: Formal Settlement | 09/12/2016 | $400.00 | 01/01/2018 | Serious | |
Penalty | F: Formal Settlement | 06/28/2016 | $400.00 | 04/01/2016 | Serious | |
Penalty | C: Contested | 04/04/2016 | $1,600.00 | 04/01/2016 | Serious | |
Penalty | Z: Issued | 03/08/2016 | $1,600.00 | 04/01/2016 | Serious |
Text For Citation: 01 Item/Group: 004A Hazard:
29 CFR 1910.110(h)(6)(i)(a): Each storage container used exclusively in service station operation shall comply with the following table which specifies minimum distances to a building and groups of buildings shall not be less than 10 feet for above ground storage tanks when building structure is not of wood frame construction. (a) South Warehouse Dock, on or about and at times preceding to September 9, 2015, 125 gallon propane tank used refueling LP forklifts was stored adjacent to exterior warehouse wall.