Violation Detail
Standard Cited: 19100119 D02 I D Process safety management of highly hazardous chemicals.
Inspection Nr: 1069909.015
Citation: 09001B
Citation Type: Serious
Abatement Date: 05/16/2019 2
Initial Penalty: $5,500.00
Current Penalty: $0.00
Issuance Date: 12/01/2015
Nr Instances: 1
Nr Exposed: 415
Related Event Code (REC):
Gravity: 5
Report ID: 0522500
Contest Date: 12/16/2015
Final Order: 03/21/2019
Emphasis:
Substance: 0170
Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
---|---|---|---|---|---|---|
Penalty | F: Formal Settlement | 03/21/2019 | $0.00 | 05/16/2019 | Serious | |
Penalty | C: Contested | 12/18/2015 | $5,500.00 | 01/03/2016 | Serious | |
Penalty | Z: Issued | 12/01/2015 | $5,500.00 | 01/03/2016 | Serious |
Text For Citation: 09 Item/Group: 001B Hazard:
29 CFR 1910.119(d)(2)(i): Information concerning the technology of the process shall include at least the following: 29 CFR 1910.119(d)(2)(i)(D): Safe upper and lower limits for such items as temperatures, pressures, flows or compositions: Information for ammonia refrigeration system lacked accurate maximum intended inventory and upper/ lower limits of system components; operating procedures lacked accurate identification of significant system components and thorough instruction as to crucial tasks; absence of written procedures for inspecting system components; failure to perform or record annual inspections of significant system components; untimely determination and documentation of corrective responses to deficiencies found during system audits; absence of refresher training.