Violation Detail
Standard Cited: 19100305 G02 III Wiring methods, components, and equipment for general use.
Inspection Nr: 1056650.015
Citation: 01014
Citation Type: Serious
Abatement Date: 1
Initial Penalty: $2,380.00
Current Penalty: $2,380.00
Issuance Date: 10/14/2015
Nr Instances: 1
Nr Exposed: 15
Related Event Code (REC):
Gravity: 5
Report ID: 0420600
Contest Date:
Final Order: 11/05/2015
Emphasis:
Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
---|---|---|---|---|---|---|
Penalty | Z: Issued | 10/14/2015 | $2,380.00 | Serious |
Text For Citation: 01 Item/Group: 014 Hazard:
29 CFR 1910.305(g)(2)(iii): Flexible cords were not connected to devices and fittings so that tension would not be transmitted to joints or terminal screws: a. At the cooling tower, employees were exposed to an electrical hazard, in that the wiring to the cooling tower were spliced with wire caps therefore transmitting pull on the joint connections, on or about 04/16/2015.