Violation Detail
Standard Cited: 19100304 F01 VIII Wiring design and protection.
Inspection Nr: 1056650.015
Citation: 01011
Citation Type: Serious
Abatement Date: 10/20/2015 2
Initial Penalty: $2,100.00
Current Penalty: $2,100.00
Issuance Date: 10/14/2015
Nr Instances: 1
Nr Exposed: 2
Related Event Code (REC):
Gravity: 1
Report ID: 0420600
Contest Date:
Final Order: 11/05/2015
Emphasis:
Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
---|---|---|---|---|---|---|
Penalty | Z: Issued | 10/14/2015 | $2,100.00 | 10/20/2015 | Serious |
Text For Citation: 01 Item/Group: 011 Hazard:
29 CFR 1910.304(f)(1)(viii): Circuit breakers used as switches in 120-volt and 277-volt, fluorescent lighting circuits were not listed and marked "SWD": a. At the machine shop, employees were exposed to an electrical hazard, in that, black extension cords were used to provide power to the fluorescent lighting in the shop directly from the breaker box located in the adjacent room from breakers that were not designated as "SWD", on or about 04/16/2015.