Standard Cited: 19100305 B01 II Wiring methods, components, and equipment for general use.
Inspection Nr: 1044418.015
Citation: 01023
Citation Type: Serious
Abatement Date: 08/25/2015 2
Initial Penalty: $3,500.00
Current Penalty: $1,400.00
Issuance Date: 08/13/2015
Nr Instances: 1
Nr Exposed: 1
Related Event Code (REC):
Gravity: 5
Report ID: 0419700
Contest Date:
Final Order: 09/08/2015
Emphasis:
Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
---|---|---|---|---|---|---|
Penalty | I: Informal Settlement | 09/08/2015 | $1,400.00 | 08/25/2015 | Serious | |
Penalty | Z: Issued | 08/13/2015 | $3,500.00 | 08/25/2015 | Serious |
Text For Citation: 01 Item/Group: 023 Hazard:
29 CFR 1910.305(b)(1)(ii): Unused openings in boxes, cabinets, or fittings were not effectively closed: a. On or about March 3, 2015, along the northwest wall of the ammonia engine room, cabinets for the compressor controllers were not closed, exposing employees to 480 volt shock hazards and arc blast hazards. b. On or about March 3, 2015, along the northwest wall of the ammonia engine room, on the 480 volt circuit breaker panel, openings on the front of the panel with exposed conductors, exposed employees to a 480 volt shock hazard.