Violation Detail
Standard Cited: 19100304 B04 II B Wiring design and protection.
Inspection Nr: 1021224.015
Citation: 01011
Citation Type: Other
Abatement Date: 06/29/2015 2
Initial Penalty: $2,550.00
Current Penalty: $1,785.00
Issuance Date: 06/03/2015
Nr Instances: 1
Nr Exposed: 5
Related Event Code (REC):
Gravity:
Report ID: 0936200
Contest Date:
Final Order: 06/29/2015
Emphasis:
Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
---|---|---|---|---|---|---|
Penalty | I: Informal Settlement | 06/29/2015 | $1,785.00 | 06/29/2015 | Other | |
Penalty | Z: Issued | 06/03/2015 | $2,550.00 | 06/29/2015 | Serious |
Text For Citation: 01 Item/Group: 011 Hazard:
29 CFR 1910.304(b)(4)(ii)(B): Where connected to a branch circuit supplying two or more receptacles or outlets, a receptacle may not supply a total cord- and plug-connected load in excess of the maximum specified in Table S-4: CWC 226, Artillery Repair: Employees were exposed to electrical shock where a 20 amp branch circuit supplying two or more receptacle outlets was supplying a load of 23.1 amps where table S-4 indicates the maximum load is 16 amps.