Violation Detail
Standard Cited: 19100307 C Hazardous (classified) locations.
Inspection Nr: 1019426.015
Citation: 01019
Citation Type: Serious
Abatement Date: 08/13/2015 2
Initial Penalty: $2,800.00
Current Penalty: $2,800.00
Issuance Date: 07/20/2015
Nr Instances: 1
Nr Exposed: 4
Related Event Code (REC):
Gravity: 10
Report ID: 0830100
Contest Date:
Final Order: 08/11/2015
Emphasis:
Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
---|---|---|---|---|---|---|
Penalty | I: Informal Settlement | 08/11/2015 | $2,800.00 | 08/13/2015 | Serious | |
Penalty | Z: Issued | 07/20/2015 | $2,800.00 | 08/13/2015 | Serious |
Text For Citation: 01 Item/Group: 019 Hazard:
29 CFR 1910.307(c): Equipment, wiring methods, and installations of equipment in hazardous (classified) locations were not intrinsically safe, approved for the hazardous (classified) location, or safe for the hazardous (classified) location: a) Dust Collector; On or about January 22, 2015 and at times prior, employees were exposed to fire and explosion hazards from unapproved electrical equipment such as, but not limited to, switches, lights, outlets, and electrical blower motors while constructing custom cabinets with combustible sawdust on elevated surfaces and ledges from one half inch in depth to approximately two inches in depth.