Violation Detail
Standard Cited: 19100106 H06 II D Flammable liquids.
Inspection Nr: 1010442.015
Citation: 01003
Citation Type: Serious
Abatement Date: 09/06/2016 2
Initial Penalty: $2,800.00
Current Penalty: $5,000.00
Issuance Date: 04/01/2015
Nr Instances: 1
Nr Exposed: 10
Related Event Code (REC):
Gravity: 10
Report ID: 0213100
Contest Date: 04/23/2015
Final Order: 01/06/2016
Emphasis:
Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
---|---|---|---|---|---|---|
Penalty | J: ALJ Decision | 01/06/2016 | $5,000.00 | 09/06/2016 | Serious | |
Penalty | C: Contested | 05/07/2015 | $2,800.00 | 06/05/2015 | Serious | |
Penalty | Z: Issued | 04/01/2015 | $2,800.00 | 06/05/2015 | Serious |
Text For Citation: 01 Item/Group: 003 Hazard:
29 CFR 1910.106(h)(6)(ii)(d): The processing area on the second floor of the building above the kettles being used to manufacture phenol-formaldehyde resins (where the formaldehyde being used to make the resin was a 37% solution classified as a Class 4 flammable liquid) was not equipped with an approved automatic sprinkler system or equivalent system.