Violation Detail
Standard Cited: 19100303 G01 I A General.
Inspection Nr: 1003600.015
Citation: 02015
Citation Type: Serious
Abatement Date: 3
Initial Penalty: $2,700.00
Current Penalty: $1,755.00
Issuance Date: 03/27/2015
Nr Instances: 2
Nr Exposed: 5
Related Event Code (REC):
Gravity: 1
Report ID: 0112000
Contest Date:
Final Order: 04/27/2015
Emphasis:
Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
---|---|---|---|---|---|---|
Penalty | I: Informal Settlement | 04/27/2015 | $1,755.00 | Serious | ||
Penalty | Z: Issued | 03/27/2015 | $2,700.00 | Serious |
Text For Citation: 02 Item/Group: 015 Hazard:
29 CFR 1910.303(g)(1)(i)(A): For electric equipment operating at 600 volts, nominal, or less to ground, and likely to require examination, adjustment, servicing, or maintenance while energized, the depth of the working space in the direction of access to live parts (as measured from the live parts where they were exposed or from the enclosure front or opening where they were enclosed) was less than indicated in Table S-1 of Subpart S of Part 1910: Waste Water Treatment Area: On, or about, October 24, 2014, a concrete foundation for a piece of equipment and railings provided on a set of fixed stairs had been installed in the working space in front of two electrical panelboards, a Westinghouse and a GE.