Violation Detail
Standard Cited: 19100124 B04 II
Inspection Nr: 1003600.015
Citation: 02003
Citation Type: Serious
Abatement Date: 3
Initial Penalty: $3,600.00
Current Penalty: $2,340.00
Issuance Date: 03/27/2015
Nr Instances: 1
Nr Exposed: 8
Related Event Code (REC):
Gravity: 5
Report ID: 0112000
Contest Date:
Final Order: 04/27/2015
Emphasis:
Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
---|---|---|---|---|---|---|
Penalty | I: Informal Settlement | 04/27/2015 | $2,340.00 | Serious | ||
Penalty | Z: Issued | 03/27/2015 | $3,600.00 | Serious |
Text For Citation: 02 Item/Group: 003 Hazard:
29 CFR 1910.124(b)(4)(ii): Mechanical ventilation did not conform to NFPA 34-1995, Standard for Dip Tanks Containing Flammable or Combustible Liquids: Comparator Area: On, or about, October 24, 2014, pvc pipe was used as part of the exhaust duct system for the Crystal Clean parts washing tank. Crystal Clean 140 Solvent was a Category 4 flammable liquid. Ref. NFPA 34 - 1995, Section 5-6.