Standard Cited: 19100119 E03 V Process safety management of highly hazardous chemicals.

This violation item has been deleted.

Inspection Nr: 1468775.015

Citation: 01003

Citation Type: Serious

Abatement Status:  

Initial Penalty: $13,494.00

Current Penalty: $0.00

Issuance Date: 09/11/2020

Nr Instances: 2

Nr Exposed: 6

Abatement Date: 10/29/2020

Gravity: 10

Report ID: 0317300

Contest Date: 10/02/2020

Final Order: 01/25/2022

Related Event Code (REC): A;R

Emphasis:


Penalty and Failure to Abate Event History
Type Latest Event Event Date Penalty Abatement Due Date Citation Type Failure to Abate Inspection
Penalty F: Formal Settlement 01/25/2022 $0.00 10/29/2020 Serious  
Penalty C: Contested 10/06/2020 $13,494.00 10/29/2020 Serious  
Penalty Z: Issued 09/11/2020 $13,494.00 10/29/2020 Serious  

Text For Citation: 01 Item/Group: 003 Hazard:

29 CFR 1910.119: The employers' PHA failed to address 29H-4 facility siting issues for the following: a) Delaware City Refinery, 4550 Wrangle Hill Road, Delaware City, DE, 19706 - Desulfurization Unit, Train 4, Heater 29-H-4:  On or about March 11 2020, the employer failed to address safe access to the fuel gas supply shutoff valves (FCV-169 and FCV-172) located on the north (oil-side) and south side (hydrogen side) of fired heater (29H-4), respectively. FCV-169 and FCV-172 are located approximately 10 feet from 29H-4 and are opened/closed manually by an operator to provide fuel gas to 29H-4. This violation contributed to a significant fire inflicting serious burn injuries on two operators and continues to create a fire/explosion hazard. b) Delaware City Refinery, 4550 Wrangle Hill Road, Delaware City, DE, 19706 - Desulfurization Unit, Train 4, Heater 29-H-4:   On or about March 11, 2020, the employer failed to address safe access to firewater monitor located on the east side of 29H-4 in the event of tube rupture. This violation contributed to a significant fire inflicting serious burn injuries on two operators and continues to create a fire/explosion hazard.

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.