Violation Detail
Standard Cited: 19100307 C02 I Hazardous (classified) locations.
Inspection Nr: 1031388.015
Citation: 01002B
Citation Type: Serious
Abatement Status: Abatement Completed
Initial Penalty: $5,390.00
Current Penalty: $0.00
Issuance Date: 08/04/2015
Nr Instances: 1
Nr Exposed: 3
Abatement Date: 08/10/2015
Gravity: 10
Report ID: 0418300
Contest Date:
Final Order: 08/31/2015
Related Event Code (REC):
Emphasis:
Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
---|---|---|---|---|---|---|
Penalty | I: Informal Settlement | 08/31/2015 | $0.00 | 08/10/2015 | Serious | |
Penalty | Z: Issued | 08/04/2015 | $5,390.00 | 08/10/2015 | Serious |
Text For Citation: 01 Item/Group: 002B Hazard:
29 CFR 1910.307(c)(2)(i): Equipment in hazardous (classified) location(s) was not approved for the ignitable or combustible properties of the specific gas, vapor, dust, or fiber that was or could be present: (a) On or about 2/6/15 - Maintenance building garage area, unapproved equipment such as the fluorescent light fixtures, household ceiling fan and light fixture, bench grinder motor, and drill press motor were used in the same area where employees manufactured a pyrotechnic composition using the Angel Fire Gerb press. The garage area was incorrectly identified as an unclassified area when it should be minimally classified as "Class II, Division 2".