Abstract: An apprentice electrician was installing an A-frame electrical meter. The base had been installed several years earlier. The meter base was not connected to a load, it but was still energized. As he was replacing the busbar jumpers in the meter base, an electrical fault occurred. The ensuing electric arc burned the employee on his hands and face. He was hospitalized for his injuries. According to the electric utility company, the fault occurred because the original wiring into the base was not installed correctly. The 480-volt, three-phase supply was running between two sides of one set of busbars in the meter base and thus more susceptible to faulting. In fact, the utility no longer used this type of meter base because they had experienced problems with it.
| Employee # | Inspection Nr | Age | Sex | Degree of Injury | Nature of Injury | Occupation |
|---|---|---|---|---|---|---|
| 1 | 102096773 | Hospitalized injury | Burn/Scald(Heat) | Electricians' apprentices |