Accident Summary Nr: 201497732 - O-Ring Fails, Worker Suffers Chemical Burns

Accident Summary Nr: 201497732 -- Report ID: 0950625 -- Event Date: 02/21/2013
Inspection NrDate OpenedSICNAICSEstablishment Name
31672237003/15/20132026311514Leprino Foods Company

Abstract: At approximately 2:45 a.m. on February 21, 2013, Employee #1, a 48-year-old cheese supervisor with Leprino Foods Company was sprayed with 180 degree Fahrenheit caustic aqueous solution used in CIP sanitation, which resulted from the failure of a sealing O-ring on a centrifugal processing pump. The system was modified during the preceding shift to provide better flow in CIP mode resulting in the script chart to appear different to Employee #1. Employee #1 called maintenance to trouble shoot the system and in the course of the investigation the airline providing pneumatic pressure to the discharge valve (pressure to open type) became disconnected causing the valve to close. The sudden closing of the discharge valve created a deadheaded condition (blanked) resulting in an impact spike in pressure by the water hammer to cause the sealing O-ring to fail. The water hammer was a fluid dynamics phenomenon where the inertia of fluid flowing in a closed system created impact pressure when the flow of discharge was suddenly stopped. By design safety factors were built into the CIP/Processing system, but were not designed to withstand the extremely high over pressures created by water hammer. Employee #1 was hospitalized, as a result of chemical burns received during the event.

Keywords: BURN, PRESSURE VESSEL, RING, PRESSURE PIPING, VALVE, CHEMICAL BURN, PRESSURE RELEASE

Employee Details
Employee # Inspection Nr Age Sex Degree of Injury Nature of Injury Occupation
1 316722370 Hospitalized injury Burn(Chemical) Supervisors, food preparation & service occupation

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.

Close