Powered by GoogleTranslate

Occupational Safety and Health Administration OSHA

Accident Report Detail

Accident: 200850030 - Employee Died Of Asphyxia From Carbon Dioxide

Accident: 200850030 -- Report ID: 0215000 -- Event Date: 02/15/1996
InspectionOpen DateSICEstablishment Name
11412501602/15/19964931Consolidated Edison Co. Of New York Inc.
An electric utility employee was working the night shift alone on a barge used to generate electric power. There was a false fire trip of the barge's carbon dioxide system, and he descended below the main deck into the fire suppression, carbon dioxide storage room. The employee was apparently resetting a carbon dioxide distribution valve and a plunger that controlled the switch for the ventilation system when he was overcome by carbon dioxide and collapsed. Evidence at the scene indicated that he made an unsuccessful attempt to escape up a vertical ladder and through an escape hatch. He died of asphyxia. The carbon dioxide had probably migrated into the storage room through the ventilation system it shared with the adjacent compartment into which the carbon dioxide had been released.
Keywords: leak, barge, maintenance, asphyxiated, ventilation, inhalation, air contamination, carbon dioxide, elec utility work
Employee # Inspection Age Sex Degree Nature Occupation
1 114125016 Fatality Asphyxia Occupation not reported

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.

Close