Accident: 200232551 - Two Sustain Burns, One Dies, In Diesel Tanker Fueling Fire

Accident: 200232551 -- Report ID: 1032500 -- Event Date: 02/02/2011
InspectionOpen DateSICEstablishment Name
31502787002/03/20115172Adamson'S, Inc.
On February 2, 2011, Employees #1 and #2 were working for a petroleum and petroleum product company. Employee #1 was on top of a transport tanker into which the vice-president of the firm was transferring #1 diesel fuel, mixing it with about 1,000 gallons (3,785 liters) of #2 diesel fuel. Employee #2 was on the ground. After "splash filling" the center tank with about 300 gallons (1,136 liters) of #1 diesel fuel, the firm's vice-president attempted to transfer the remainder of the #1 diesel to the truck's front tank. He was going to do this task through "switch loading." The front tank had previously contained 3,500 gallons (13,248 liters) of unleaded gasoline. Now, it contained only vapors. An explosion occurred, and the resulting fire consumed the 1,000 gallons (3,785 liters) of gasoline and 1,300 gallons (4,921 liters) of diesel fuel in the tanker trailer. The older diesel tank truck was severely damaged, but it still contained about 1,000 gallons (3,785 liters) of #1 diesel. Employee #1, on top of the tanker, was killed in the fire. The fire spread to Employee #2, who was on the ground. His clothing caught on fire, but he escaped with only minor burns. Several causes were believed to have led to the generation, accumulation, and discharge of static electricity in the presence of flammable gasoline vapors, gasoline liquid, and diesel liquid. They included, but they were not limited to these: 1. There was no bonding between the two vehicles. 2. There was no potential grounding of the tanker trailer to the three inch (7.6 cm) gasoline line hooked to the 10,000 gallon (37,854 liter) storage tank being filled. 3. The transfer of 300 gallons (1,136 liters) of #1 diesel fuel, a known static accumulator, was done by "splash filling"; that is, without the use of a downspout. 4. There was an attempt to "switch load" the diesel fuel into the gasoline tank, which contained vapors with a flash point of minus 45 degrees Fahrenheit (minus 43 degrees Celsius). 5. There was an accumulation of static electricity on the employee making the transfer. The static electricity built up on his winter clothing and insulated boots, in zero degree Fahrenheit (minus 18 degree Celsius) weather, with low humidity. 6. Accordingly, there was a static spark with an estimated two to ten times the energy needed to ignite gasoline.
Keywords: burn, protective grounding, flammable liquid, flammable vapors, refueling, fire, diesel truck, explosion, truck, gasoline
Employee # Inspection Age Sex Degree Nature Occupation
1 315027870 Fatality Asphyxia Truck drivers, heavy

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.

Close