Occupational Safety and Health Administration OSHA

Accident Report Detail

Accident: 170695209 - Burn - Electrical Fault In Test Equipment

Accident: 170695209 -- Report ID: 0950645 -- Event Date: 10/01/1992
InspectionOpen DateSICEstablishment Name
12005744310/27/19922037Pick Sweet Foods
A BOILER WORKER ASKED THE ONLY ELECTRICIAN ON DUTY TO REPAIR A COMPRESSOR. THE ELECTRICIAN WENT TO THE POWER ROOM AND OPENED THE COVER TO THE FUSES ON THE C-3 FREEZING HIGH STAGE COMPRESSOR (WITH AN ITE 5000-VOLT MOTOR STARTER) NEEDING REPAIR. AFTER OPENING THE COVER, HE HELD THE INTERLOCK SWITCH CLOSED WITH ONE HAND AND PUT A 600-VOLT WIGGY SQUARE D TESTER TO TEST THE LARGE FUSE. THE TESTER FAILED, BURNING HIS HANDS AND FACE. THE VOLTAGE ON THE PANELBOARD ON WHICH HE WAS WORKING WAS 4160 VOLTS (AS STATED ON THE PANELBOARD COVER); HOWEVER, THE ELECTRICIAN HAD NO EXPERIENCE OR TRAINING TO WORK ON ANYTHING OVER 460 VOLTS. THE TESTER THE ELECTRICIAN WAS USING WAS THE HIGHEST VOLTAGE RATED ONE AVAILABLE. THE EMPLOYEE WAS HOSPITALIZED FOR HIS INJURIES.
Keywords: burn, e gi v, electric arc, electrical, electrical testing, electrician, electrical work, test equipment, electrical fault
Employee # Inspection Age Sex Degree Nature Occupation
1 120057443 Hospitalized injury Burn/Scald(Heat) Electricians

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.

Close