Accident Summary Nr: 170066286 - ELECTRIC SHOCK - DIRECT CONTACT WITH ENERGIZED PARTS

Accident Summary Nr: 170066286 -- Report ID: 0352410 -- Event Date: 01/06/1993
Inspection NrDate OpenedSICNAICSEstablishment Name
10445479801/07/199349110Delmarva Power & Light Company

Abstract: A FOUR-PERSON CREW WAS WORKING IN A SUBSTATION, REPAIRING A PAD-MOUNTED CIRCUIT BREAKER (#510). THE SYSTEM OPERATOR HAD GRANTED CLEARANCE TO REMOVE POWER TO BREAKER #510, AND CIRCUITS #509 AND #511 WERE OPENED AS WELL. TAGS WERE DISPLAYED, AND THE CIRCUITS WERE DEENERGIZED AND VISIBLY GROUNDED. THE BUSHINGS ATOP THE BREAKER WERE DISCONNECTED FROM THEIR LEADS BY ONE OF THE EMPLOYEES. THE BREAKER WAS REPAIRED, AND THE FOUR EMPLOYEES WENT TO THE SUBSTATION CONTROL HOUSE TO CONTACT THE SYSTEM OPERATOR BY TELEPHONE. THE SYSTEM OPERATOR GRANTED APPROVAL TO PLACE THE REPAIRED BREAKER BACK IN SERVICE. BEFORE DEPARTING THE CONTROL HOUSE, THE EMPLOYEES DISCUSSED WHAT NEEDED TO BE DONE TO COMPLETE THE TASK. WHEN THEY LEFT THE CONTROL HOUSE, IT WAS COMPLETELY DARK OUTSIDE. THE EMPLOYEE WHO HAD DISCONNECTED THE BUSHINGS EXITED FIRST AND WENT TO THE WORK AREA. THE OTHER EMPLOYEES WENT TO THEIR TRUCKS TO GET TOOLS AND EQUIPMENT AND TO REFOCUS THE TRUCK-MOUNTED SPOTLIGHTS ON THE WORK AREA. THE EMPLOYEE WHO WENT TO THE BREAKER HAD UNKNOWINGLY GONE TO BREAKER #500 RATHER THAN TO #510. BREAKER #500, WHICH REMAINED ENERGIZED, WAS ABOUT 10 FEET AWAY FROM BREAKER #510, AND IT WAS ALMOST IDENTICAL IN APPEARANCE. ASSUMING THAT HE WAS AT BREAKER #510, THE EMPLOYEE CLIMBED THE BREAKER TO RECONNECT THE CABLE LEADS. HE REACHED FOR A BUSHING TO PULL HIMSELF UP AND RECEIVED AN ELECTRIC SHOCK FROM THE ENERGIZED PORTION OF THE 7200-VOLT BUSHING. THE EMPLOYEE WAS HOSPITALIZED FOR HIS INJURY.

Keywords: ELECTRICAL, POWER LINE WORKER, LOCKOUT, E PTD, SUBSTATION, CIRCUIT BREAKER, LIGHTING, ELEC UTILITY WORK, ELECTRIC SHOCK

Employee Details
Employee # Inspection Nr Age Sex Degree of Injury Nature of Injury Occupation
1 104454798 Hospitalized injury Electric Shock Electrical and electronic technicians

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.

Close