Accident Summary Nr: 170000657 - BURN - ELECTRICAL FAULT IN CONDUIT
Inspection Nr | Date Opened | SIC | NAICS | Establishment Name |
---|---|---|---|---|
111318531 | 12/09/1992 | 4911 | 0 | Puget Sound Power & Light Co |
Abstract: An electric utility employee was using a Milwaukee Sawzall to cut two 150-millimeter-diameter conduits at the bottom of a trench. A second employee was helping him. The blade on the saw was too long; and, as it cut through the two empty conduits, its tip also penetrated a third conduit that was carrying a 34.5-kilovolt cable. This caused an electrical fault, and the ensuing electric arc caused flash burns to both employees.
Employee # | Inspection Nr | Age | Sex | Degree of Injury | Nature of Injury | Occupation |
---|---|---|---|---|---|---|
1 | 111318531 | Non Hospitalized injury | Burn/Scald(Heat) | Electrical power installers and repairers | ||
2 | 111318531 | Non Hospitalized injury | Burn/Scald(Heat) | Electrical power installers and repairers |