Accident: 14485619 - Burn - Electrical Fault In Panelboard

Accident: 14485619 -- Report ID: 0213600 -- Event Date: 04/09/1986
InspectionOpen DateSICEstablishment Name
10018376304/10/19863531Trojan Industries Inc.
On February 21, 1986, two maintenance workers were replacing a fuse block panel in a 480-volt, 60-ampere, three-phase panelboard. The panelboard was mounted 6.4 meters above grade. The employees were working on a Lift-A-Loft platform. While they were working, one of them caused a phase-to-ground fault. The fault tripped a 480-volt, 2000-ampere, three-phase breaker, but not before the ensuing electric arc melted a potion of the panelboard and severely burned both employees. The employees were hospitalized for their injuries. On April 9, 1986, one of the employees died of his injuries, and the other was released from the hospital.
Keywords: burn, clothing, electric arc, e gi iv, electrical, electrical work, lockout, electrical fault
Employee # Inspection Age Sex Degree Nature Occupation
1 100183763 Fatality Burn/Scald(Heat) Machinery maintenance occupations
2 100183763 Hospitalized injury Burn/Scald(Heat) Machinery maintenance occupations

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.

Close