Accident Report Detail
Accident: 14350979 - Crushed Between Forklift And Elevator Door Frame
Accident: 14350979 -- Report ID: 0418300 -- Event Date: 04/25/1985 | |||||||
Inspection | Open Date | SIC | Establishment Name | ||||
---|---|---|---|---|---|---|---|
2180586 | 04/25/1985 | 2789 | Workshops, Inc. | ||||
EMPLOYEE #1, A FORKLIFT OPERATOR, WAS DRIVING ONTO AN 8,000 POUND CAPACITY FREIGHT ELEVATOR. SHE WAS HALFWAY INTO THE ELEVATOR WHEN IT STARTED UP. THE FORKLIFT'S OVERHEAD PROTECTION, WHICH WAS FABRICATED OUT OF 1 1/2 INCH STEEL TUBING, WAS BENT AND BROKEN DOWN ONTO EMPLOYEE #1 WHEN THE FORKLIFT BECAME WEDGED BETWEEN THE ELEVATOR AND THE SECOND FLOOR LANDING. THE COMPANY HAD NO MAINTENANCE PROGRAM ON THE ELEVATOR. APPARENTLY, OVER THE PAST SEVERAL MONTHS, TWO ELECTRICAL RELAYS BECOME OVERHEATED AND MELTED THE INSULATION ON THE WIRES. THE WIRES FUSED, CAUSING CURRENT TO BE SUPPLIED TO THE LINE STARTER (BYPASSING THE SAFETY DEVICES) AND STARTING THE ELEVATOR. | |||||||
Keywords:
maintenance, overhead protection, crushed, industrial truck, elevator
| |||||||
Employee # | Inspection | Age | Sex | Degree | Nature | Occupation | |
1 | 2180586 | Fatality | Bruise/Contus/Abras | Occupation not reported |