Accident: 14232714 - Employee Killed During Tank Explosion

Accident: 14232714 -- Report ID: 0316400 -- Event Date: 12/31/1991
InspectionOpen DateSICEstablishment Name
10059698001/01/19922869Union Carbide Chemicals & Plastics
Employee #1, the basement operator at a powerhouse, was purging the liquid residue from the betene entrainment tank to the #16 boiler. Water and steam inadvertently got into the knockout pot, and materials that react to water, such as, but not limited to, acetic anhydride and diketene were in the tank. A reaction occurred, releasing flammable and hazardous materials into the atmosphere through a safety relief valve. The pressure relief device was only sized for an external fire, not a chemical reaction. As a result, the safety relief valves could not withstand the reaction. The overpressurization caused the steel pot to fail and explode. Employee #1 was killed.
Keywords: safety relief valve, toxic atmosphere, equipment failure, explosion, chemical reaction, high pressure, valve, tank, accidental discharge
Employee # Inspection Age Sex Degree Nature Occupation
1 100596980 Fatality Strain/Sprain Occupation not reported

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.

Close