Violation Detail
Standard Cited: 19100305 G01 IV A Wiring methods, components, and equipment for general use.
Inspection Nr: 1528071.015
Citation: 01005B
Citation Type: Serious
Abatement Date: 11/23/2021 2
Initial Penalty: $5,461.00
Current Penalty: $0.00
Issuance Date: 10/27/2021
Nr Instances: 4
Nr Exposed: 5
Related Event Code (REC):
Gravity: 10
Report ID: 0627100
Contest Date:
Final Order: 11/24/2021
Emphasis:
Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
---|---|---|---|---|---|---|
Penalty | I: Informal Settlement | 11/24/2021 | $0.00 | 11/23/2021 | Serious | |
Penalty | Z: Issued | 10/27/2021 | $5,461.00 | 11/23/2021 | Serious |
Text For Citation: 01 Item/Group: 005B Hazard:
29 CFR 1910.305(g)(1)(iv)(A): Flexible cords and/or cables were used as a substitute for the fixed wiring of a structure: On or about April 28, 2021, employees were exposed to electrical shock and burn hazards in that: a. On the CME pellet machine, flexible cords were used in place of fixed wiring to supply power to auger motors. b. On the 575ST Karsh mixer by the hammer mill, a flexible cord was used in place of fixed wiring to supply power to the Avery Weigh-Tronix XR 4500 scale. c. At the THMR Kwikcutter 449 mixer loading station, flexible cords were used in place of fixed wiring for the World Weigh BWS scale, and the florescent bulbs. d. In the packaging room, flexible cords were used in place of fixed wiring for the Fuji stacking robot, the conveyor belt, and the standing fans.