Violation Detail
Standard Cited: 19100106 E06 II Flammable liquids.
Inspection Nr: 1443554.015
Citation: 01002B
Citation Type: Serious
Abatement Date: 05/19/2020 2
Initial Penalty: $0.00
Current Penalty: $0.00
Issuance Date: 05/05/2020
Nr Instances: 1
Nr Exposed: 22
Related Event Code (REC): C
Gravity: 10
Report ID: 0627100
Contest Date:
Final Order: 05/28/2020
Emphasis:
Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
---|---|---|---|---|---|---|
Penalty | I: Informal Settlement | 05/28/2020 | $0.00 | 05/19/2020 | Serious | |
Penalty | Z: Issued | 05/05/2020 | $0.00 | 05/19/2020 | Serious |
Text For Citation: 01 Item/Group: 002B Hazard:
29 CFR 1910.106(e)(6)(ii): Category 1 or 2 flammable liquids, or Category 3 flammable liquids with a flashpoint below 100 °F (37.8 °C), were dispensed into containers without the nozzle and container being electrically interconnected: In the shop, where the employer did not ensure that 55-gallon drums of flammable liquids and gases including but not limited to Propylene, B50AZ6 primer, B50AV11 primer and P-1400 thinner were effectively bonded and grounded prior to employees dispensing to prevent discharge of sparks or static electricity.