Violation Detail
Standard Cited: 19100106 D04 IV Flammable liquids.
Inspection Nr: 1436552.015
Citation: 01001C
Citation Type: Serious
Abatement Date: 07/02/2020 2
Initial Penalty: $0.00
Current Penalty: $0.00
Issuance Date: 04/03/2020
Nr Instances: 1
Nr Exposed: 5
Related Event Code (REC):
Gravity: 5
Report ID: 0418100
Contest Date: 05/07/2020
Final Order: 07/07/2021
Emphasis:
Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
---|---|---|---|---|---|---|
Penalty | F: Formal Settlement | 07/07/2021 | $0.00 | 07/02/2020 | Serious | |
Penalty | C: Contested | 05/14/2020 | $0.00 | 07/02/2020 | Serious | |
Penalty | Z: Issued | 04/03/2020 | $0.00 | 07/02/2020 | Serious |
Text For Citation: 01 Item/Group: 001C Hazard:
29 CFR 1910.106(d)(4)(iv): Ventilation. Every inside storage room shall be provided with either a gravity or a mechanical exhaust ventilation system. Such system shall be designed to provide for a complete change of air within the room at least six times per hour. Creative Multicare, Inc. - On or about March 6, 2020, in the inside storage room and mixing room located at 820 Rock Quarry Road, Stockbridge, GA, the inside storage room did not have gravity or mechanical exhaust ventilation exposing workers to chemical, explosion, and fire hazards. In accordance with 29 CFR 1903.19(c), abatement certification is required for this violation (using the CERTIFICATION OF CORRECTIVE ACTION WORKSHEET).