Violation Detail
Standard Cited: 19100106 D04 III Flammable liquids.
Inspection Nr: 1436552.015
Citation: 01001B
Citation Type: Serious
Abatement Date: 07/02/2020 2
Initial Penalty: $0.00
Current Penalty: $0.00
Issuance Date: 04/03/2020
Nr Instances: 1
Nr Exposed: 5
Related Event Code (REC):
Gravity: 5
Report ID: 0418100
Contest Date: 05/07/2020
Final Order: 07/07/2021
Emphasis:
Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
---|---|---|---|---|---|---|
Penalty | F: Formal Settlement | 07/07/2021 | $0.00 | 07/02/2020 | Serious | |
Penalty | C: Contested | 05/14/2020 | $0.00 | 07/02/2020 | Serious | |
Penalty | Z: Issued | 04/03/2020 | $0.00 | 07/02/2020 | Serious |
Text For Citation: 01 Item/Group: 001B Hazard:
29 CFR 1910.106(d)(4)(iii): Wiring. Electrical wiring and equipment located in inside storage rooms used for Category 1 or 2 flammable liquids, or Category 3 flammable liquids with a flashpoint below 100 °F (37.8 °C), shall be approved under subpart S of this part for Class I, Division 2 Hazardous Locations; for Category 3 flammable liquids with a flashpoint at or above 100 °F (37.8 °C) and Category 4 flammable liquids, shall be approved for general use. Creative Multicare, Inc - On or about March 6, 2020, in the inside storage room and mixing room located at 820 Rock Quarry Road, Stockbridge, GA, employees stored and dispensed flammable liquids for mixing, and electrical wiring were not approved for Class I Division II. In accordance with 29 CFR 1903.19(c), abatement certification is required for this violation (using the CERTIFICATION OF CORRECTIVE ACTION WORKSHEET).