Violation Detail
Standard Cited: 19100303 G01 I C General.
Inspection Nr: 1381123.015
Citation: 01006C
Citation Type: Serious
Abatement Date: 3
Initial Penalty: $0.00
Current Penalty: $0.00
Issuance Date: 05/16/2019
Nr Instances: 1
Nr Exposed: 1
Related Event Code (REC):
Gravity: 5
Report ID: 0112000
Contest Date:
Final Order: 06/04/2019
Emphasis:
Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
---|---|---|---|---|---|---|
Penalty | I: Informal Settlement | 06/04/2019 | $0.00 | Serious | ||
Penalty | Z: Issued | 05/16/2019 | $0.00 | Serious |
Text For Citation: 01 Item/Group: 006C Hazard:
29 CFR 1910.303(g)(1)(i)(C): For electric equipment operating at 600 volts, nominal, or less to ground, and likely to require examination, adjustment, servicing, or maintenance while energized, the width of work space was not clear and did not extend from the grade, floor, or platform to the height required by paragraph (g)(1)(vi) of 29 CFR 1910.303: Fabrication Shop: On, or about, March 7, 2019, a transformer had been installed in the working space for the Siemens 600 volt panelboard. The transformer projected 10.5 inches from the face of the panelboard.