Violation Detail
Standard Cited: 19100303 G01 I A General.
Inspection Nr: 1375672.015
Citation: 01013A
Citation Type: Serious
Abatement Date: 1
Initial Penalty: $2,874.00
Current Penalty: $1,437.00
Issuance Date: 06/07/2019
Nr Instances: 3
Nr Exposed: 8
Related Event Code (REC):
Gravity: 1
Report ID: 0112000
Contest Date:
Final Order: 07/09/2019
Emphasis:
Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
---|---|---|---|---|---|---|
Penalty | I: Informal Settlement | 07/09/2019 | $1,437.00 | Serious | ||
Penalty | Z: Issued | 06/07/2019 | $2,874.00 | Serious |
Text For Citation: 01 Item/Group: 013A Hazard:
29 CFR 1910.303(g)(1)(i)(A): For electric equipment operating at 600 volts, nominal, or less to ground, and likely to require examination, adjustment, servicing, or maintenance while energized, the depth of the working space in the direction of access to live parts (as measured from the live parts where they were exposed or from the enclosure front or opening where they were enclosed) was less than indicated in Table S-1 of Subpart S of Part 1910: A. Building 1: On, or about, February 13, 2019, a Holland spin dryer and mounting rails were located in the working space in front of the General Electrical panelboard. B. Building 3: On, or about, February 13, 2019, electrical Panels near Line 23 Finish End: Stanchions and metal banding were installed in the working space in front of four General Electric panelboards. C. Building 3, Main Aisle: On, or about, February 13, 2019, a metal barrier had been installed on the floor in the working space in front of three General Electric panelboards.