Violation Detail
Standard Cited: 19100305 J02 VII Wiring methods, components, and equipment for general use.
Inspection Nr: 1326689.015
Citation: 01005E
Citation Type: Serious
Abatement Date: 11/28/2018 2
Initial Penalty: $0.00
Current Penalty: $0.00
Issuance Date: 10/10/2018
Nr Instances: 1
Nr Exposed: 1
Related Event Code (REC):
Gravity: 5
Report ID: 0112000
Contest Date:
Final Order: 10/30/2018
Emphasis:
Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
---|---|---|---|---|---|---|
Penalty | I: Informal Settlement | 10/30/2018 | $0.00 | 11/28/2018 | Serious | |
Penalty | Z: Issued | 10/10/2018 | $0.00 | 11/28/2018 | Serious |
Text For Citation: 01 Item/Group: 005E Hazard:
29 CFR 1910.305(j)(2)(vii): A receptacle installed in a wet location where the product intended to be plugged into it was to be attended while in use (for example, portable tools) did not have an enclosure that was weatherproof when the attachment plug cap was removed: A. On or about July 2, 2018, Upholstery Cleaning Area: An unused upper receptacle in a 2-receptacle wall-mounted outlet box under electrical breaker boxes was not covered during upholstery cleaning operations. Water spray from upholstery cleaning could enter the energized outlet, exposing employees standing in wet areas to electric shock hazards.