Violation Detail
Standard Cited: 19100303 G01 I B General.
Inspection Nr: 1091666.015
Citation: 03006B
Citation Type: Serious
Abatement Date: 04/04/2016 2
Initial Penalty: $0.00
Current Penalty: $0.00
Issuance Date: 02/17/2016
Nr Instances: 1
Nr Exposed: 4
Related Event Code (REC):
Gravity: 5
Report ID: 0112000
Contest Date:
Final Order: 03/14/2016
Emphasis:
Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
---|---|---|---|---|---|---|
Penalty | I: Informal Settlement | 03/14/2016 | $0.00 | 04/04/2016 | Serious | |
Penalty | Z: Issued | 02/17/2016 | $0.00 | 04/04/2016 | Serious |
Text For Citation: 03 Item/Group: 006B Hazard:
29 CFR 1910.303(g)(1)(i)(B): For electric equipment operating at 600 volts, nominal, or less to ground, and likely to require examination, adjustment, servicing, or maintenance while energized, the width of the working space in front of electrical equipment was less than the width of the equipment or 762 mm (30 inches), whichever was greater : Heat Treat: On, or about, September 21, 2015, Panel #13, a Challenger 208 volt panelboard was not provided with adequate working space in that a metal file cabinet was located on the left side of the panel and a reel dispenser was located to the right. The required working space width was 30 inches wide.