Violation Detail
Standard Cited: 19100305 G02 II Wiring methods, components, and equipment for general use.
Inspection Nr: 1047229.015
Citation: 02008
Citation Type: Other
Abatement Date: 08/04/2015 2
Initial Penalty: $0.00
Current Penalty: $0.00
Issuance Date: 07/29/2015
Nr Instances: 3
Nr Exposed: 50
Related Event Code (REC):
Gravity:
Report ID: 0420600
Contest Date:
Final Order: 08/19/2015
Emphasis:
Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
---|---|---|---|---|---|---|
Penalty | I: Informal Settlement | 08/19/2015 | $0.00 | 08/04/2015 | Other | |
Penalty | Z: Issued | 07/29/2015 | $0.00 | 08/04/2015 | Other |
Text For Citation: 02 Item/Group: 008 Hazard:
29 CFR 1910.305(g)(2)(ii): Flexible cords were not used only in continuous lengths without splice or tap: a. Compressor area, employees were exposed to an electrical hazard, in that, the wiring to the compressor air tank water separator was spliced with electrical tape and wire caps, on or about 03/18/2015. b. Notcher area, employees were exposed to an electrical hazard, in that, the wiring to the exterior light outside the overhang was spliced with electrical wire caps, on or about 03/18/2015. c. At the catwalk after the de-stacking area, employees were exposed to an electrical hazard, in that, the wiring to the light mounted around the catwalk was spliced with electrical wire caps only, on or about 03/18/2015.