Violation Detail
Standard Cited: 19100304 F01 V Wiring design and protection.
Inspection Nr: 1119628.015
Citation: 03013
Citation Type: Serious
Abatement Status: Abatement Completed
Initial Penalty: $5,000.00
Current Penalty: $5,000.00
Issuance Date: 07/13/2016
Nr Instances: 50
Nr Exposed: 5
Abatement Date: 08/29/2016
Gravity: 5
Report ID: 0112000
Contest Date: 08/04/2016
Final Order: 04/17/2017
Related Event Code (REC): C
Emphasis:
Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
---|---|---|---|---|---|---|
Penalty | F: Formal Settlement | 04/17/2017 | $5,000.00 | 08/29/2016 | Serious | |
Penalty | C: Contested | 08/05/2016 | $5,000.00 | 08/29/2016 | Serious | |
Penalty | Z: Issued | 07/13/2016 | $5,000.00 | 08/29/2016 | Serious |
Text For Citation: 03 Item/Group: 013 Hazard:
29 CFR 1910.304(f)(1)(v): The employer did not ensure that fuses and circuit breakers were so located or shielded that employees will not be burned or otherwise injured by their operation. Mezzanine Electrical Room: On, or about, January 15, 2016, fuse holders and cartridge fuses throughout the room were not provided with enclosures or shielding to protect employees from arcs and/or flying objects in the event of the operation of the over-current device.