Standard Cited: 19100304 F01 I Wiring design and protection.
Inspection Nr: 1119628.015
Citation: 03012
Citation Type: Serious
Abatement Status: Abatement Completed
Initial Penalty: $4,000.00
Current Penalty: $2,400.00
Issuance Date: 07/13/2016
Nr Instances: 1
Nr Exposed: 5
Abatement Date: 08/29/2016
Gravity: 5
Report ID: 0112000
Contest Date:
Final Order: 08/03/2016
Related Event Code (REC):
Emphasis:
Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
---|---|---|---|---|---|---|
Penalty | I: Informal Settlement | 08/03/2016 | $2,400.00 | 08/29/2016 | Serious | |
Penalty | Z: Issued | 07/13/2016 | $4,000.00 | 08/29/2016 | Serious |
Text For Citation: 03 Item/Group: 012 Hazard:
29 CFR 1910.304(f)(1)(i): Conductors and equipment were not protected from overcurrent in accordance with their ability to safely conduct current: Mezzanine Electrical Room: On, or about January 15, 2016, Type SOOW flexible cord was wired onto the load side of a 60 ampere Square D circuit breaker in the Square D 480 volt I-Line panelboard provided for Coater 1 in order to energize IR heater used on the Pilot Line. The cord was only rated for a load of 45 amperes.