Standard Cited: 19100303 G02 II General.
Inspection Nr: 1119628.015
Citation: 03010
Citation Type: Serious
Abatement Status: Abatement Completed
Initial Penalty: $7,000.00
Current Penalty: $4,200.00
Issuance Date: 07/13/2016
Nr Instances: 1
Nr Exposed: 2
Abatement Date: 08/29/2016
Gravity: 10
Report ID: 0112000
Contest Date:
Final Order: 08/03/2016
Related Event Code (REC): C
Emphasis:
Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
---|---|---|---|---|---|---|
Penalty | I: Informal Settlement | 08/03/2016 | $4,200.00 | 08/29/2016 | Serious | |
Penalty | Z: Issued | 07/13/2016 | $7,000.00 | 08/29/2016 | Serious |
Text For Citation: 03 Item/Group: 010 Hazard:
29 CFR 1910.303(g)(2)(ii): In locations where electric equipment was likely to be exposed to physical damage, enclosures or guards were not so arranged and of such strength as to prevent such damage: Mezzanine Electrical Room: On, or about, January 15, 2016, employees routinely calibrated LEL (lower explosive limit) sensors located in incinerator ductwork that ran through the room. Employees worked above live, exposed electrical equipment for Coater #2 that was not protected from physical damage in the event that either a hand tool or calibration gas cylinder was accidently dropped.