Violation Detail
Standard Cited: 19100305 A02 IX Wiring methods, components, and equipment for general use.
Inspection Nr: 1374648.015
Citation: 03006A
Citation Type: Other
Abatement Date: 08/14/2019 2
Initial Penalty: $5,834.00
Current Penalty: $0.00
Issuance Date: 07/17/2019
Nr Instances: 4
Nr Exposed: 14
Related Event Code (REC):
Gravity:
Report ID: 0521100
Contest Date:
Final Order: 08/08/2019
Emphasis:
Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
---|---|---|---|---|---|---|
Penalty | I: Informal Settlement | 08/08/2019 | $0.00 | 08/14/2019 | Other | |
Penalty | Z: Issued | 07/17/2019 | $5,834.00 | 08/14/2019 | Serious |
Text For Citation: 03 Item/Group: 006A Hazard:
29 CFR 1910.305(a)(2)(ix): All lamps for general illumination shall be protected from accidental contact or breakage by a suitable fixture or lampholder with a guard. Brass shell, paper-lined sockets, or other metal-cased sockets may not be used unless the shell is grounded. a. On or about February 11, 2019, a compact fluorescent light bulb in the sawmill basement near the Chipper Office was not protected from accidental contact or breakage by a suitable fixture or guard. b. On or about February 11, 2019, two 4 foot fluorescent tubes in the sawmill basement near the Chipper Office were not protected from accidental contact or breakage by a suitable fixture or guard. c. On or about February 11, 2019, two 4 foot fluorescent tubes in the sawmill basement near the near Head Saw #2 Pit were not protected from accidental contact or breakage by a suitable fixture or guard. d. On or about February 11, 2019, two 4 foot fluorescent tubes in the sawmill basement near the near Head Saw #2 Pit were not protected from accidental contact or breakage by a suitable fixture or guard.