Violation Detail
Standard Cited: 19100303 B01 I General.
Inspection Nr: 1119628.015
Citation: 03006
Citation Type: Serious
Abatement Status: Abatement Completed
Initial Penalty: $5,000.00
Current Penalty: $5,000.00
Issuance Date: 07/13/2016
Nr Instances: 2
Nr Exposed: 5
Abatement Date: 08/29/2016
Gravity: 5
Report ID: 0112000
Contest Date: 08/04/2016
Final Order: 04/17/2017
Related Event Code (REC): C
Emphasis:
Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
---|---|---|---|---|---|---|
Penalty | F: Formal Settlement | 04/17/2017 | $5,000.00 | 08/29/2016 | Serious | |
Penalty | C: Contested | 08/05/2016 | $5,000.00 | 08/29/2016 | Serious | |
Penalty | Z: Issued | 07/13/2016 | $5,000.00 | 08/29/2016 | Serious |
Text For Citation: 03 Item/Group: 006 Hazard:
29 CFR 1910.303(b)(1)(i): Suitability for installation and use of electrical equipment was not evidenced by listing, labeling or other means for the identified purpose: Mezzanine Electrical Room: On, or about, January 15, 2016, the following electrical equipment had not been examined and listed for use in accordance with Underwriter's Laboratory Standard 508, Industrial Control Equipment: A. Square D contactor labeled CR-2 mounted next to Pilot Coater Main Disconnect: This specific purpose contactor was not contained in a control panel and therefore had not been properly applied and installed in that it was required to be installed in a control panel per the manufacturer. B. Square D combination motor controllers provided for the Smith Incinerator: The combination motor controllers provided for the Purge Fan and Hydraulic Pump were not installed in the configuration that had been examined and listed to meet UL standards per the manufacturer as per the National Electric Code -2014, Article 430, Motors, Motor Circuits, and Controllers.