Violation Detail
Standard Cited: 19100303 G01 I B General.
Inspection Nr: 1374648.015
Citation: 03005C
Citation Type: Other
Abatement Status: Abatement Completed
Initial Penalty: $0.00
Current Penalty: $0.00
Issuance Date: 07/17/2019
Nr Instances: 2
Nr Exposed: 14
Abatement Date: 08/14/2019
Gravity:
Report ID: 0521100
Contest Date:
Final Order: 08/08/2019
Related Event Code (REC):
Emphasis:
Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
---|---|---|---|---|---|---|
Penalty | I: Informal Settlement | 08/08/2019 | $0.00 | 08/14/2019 | Other | |
Penalty | Z: Issued | 07/17/2019 | $0.00 | 08/14/2019 | Serious |
Text For Citation: 03 Item/Group: 005C Hazard:
29 CFR 1910.303(g)(1)(i)(B): The width of working space in front of the electric equipment shall be the width of the equipment or 762 mm (30 in.), whichever is greater. In all cases, the working space shall permit at least a 90-degree opening of equipment doors or hinged panels; and a. On or about March 19, 2019, the width of the working space in front of the electric equipment in the Molding Room was less than 30 inches. The distance between the measuring table and the electrical switchboard was approximately 25 inches.