Violation Detail
Standard Cited: 19100303 F02 General.
Inspection Nr: 1204677.015
Citation: 03002
Citation Type: Other
Abatement Date: 3
Initial Penalty: $0.00
Current Penalty: $0.00
Issuance Date: 07/11/2017
Nr Instances: 3
Nr Exposed: 25
Related Event Code (REC):
Gravity:
Report ID: 0418100
Contest Date:
Final Order: 07/28/2017
Emphasis:
Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
---|---|---|---|---|---|---|
Penalty | I: Informal Settlement | 07/28/2017 | $0.00 | Other | ||
Penalty | Z: Issued | 07/11/2017 | $0.00 | Other |
Text For Citation: 03 Item/Group: 002 Hazard:
29 CFR 1910.303(f)(2): Each service, feeder, and branch circuit, at its disconnecting means or overcurrent device, was not legibly marked to indicate its purpose, nor located and arranged so the purpose was evident: On or about 1/23/2017, throughout the facility, employees were exposed to electrical hazards in the case of an emergency where the electrical disconnects were not marked or identifiable from location in areas including but not limited to: a. 480 V by Buggo machine b. welding bay 1 - 480 V box c. outside welding bay 1 - Square D, marked 480 V 60 A d. welding bay 3 - 208 V /120 V, 3 phase, 4 wire