Violation Detail
Standard Cited: 19260350 A10 Gas welding and cutting.
Inspection Nr: 1271630.015
Citation: 03001B
Citation Type: Repeat
Abatement Status: Not Completed - Worksite Changed
Initial Penalty: $0.00
Current Penalty: $0.00
Issuance Date: 04/17/2018
Nr Instances: 1
Nr Exposed: 4
Abatement Date: 04/27/2018
Gravity: 10
Report ID: 0317000
Contest Date:
Final Order: 05/15/2018
Related Event Code (REC):
Emphasis:
Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
---|---|---|---|---|---|---|
Penalty | Z: Issued | 04/17/2018 | $0.00 | 04/27/2018 | Repeat |
Text For Citation: 03 Item/Group: 001B Hazard:
29 CFR 1926.350(a)(10): Oxygen cylinders in storage shall be separated from fuel-gas cylinders or combustible materials (especially oil or grease), a minimum distance of 20 feet (6.1 m) or by a noncombustible barrier at least 5 feet (1.5 m) high having a fire-resistance rating of at least one-half hour: a) Jobsite: The employer did not ensure that stored oxygen and acetylene cylinders were separated by distance or a suitable barrier exposing employee to explosion hazards. The compressed gas cylinders were touching when being stored. Condition was observed on or about 19 OCT 2017 and 3 NOV 2017. Hua Da Construction, Inc. was previously cited for a violation of this occupational safety and health standard or its equivalent standard 1926.350(a)(10) which was contained in OSHA inspection number 1143244, citation number 1, item number 1-c and was affirmed as a final order on 09 MAY 2016, with respect to a workplace located at 934 Arch Street, Philadelphia.